Wait! Donโ€™t Go Yet! ๐Ÿ‘‹

We see you eyeing those adorable outfits! ๐Ÿ˜ Before you leave, hereโ€™s 10% OFF your first order!

Hurry, your little oneโ€™s next favorite outfit is waiting! ๐Ÿ›๏ธโœจ

Railway Battery Charger – Discharger

110V-155V upto 30-500 Amp

MAC Power Systems designs and manufactures high-reliability industrial Battery Chargers and Charger-Cum-Dischargers for critical power applications. Built with conservative design principles and premium components, our systems ensure failsafe operation, long service life, and consistent performance under demanding conditions.

Our chargers are available in standard and customized configurations, suitable for a wide range of industrial and infrastructure, Railway applications.

Request Quote

  • Premium Quality
  • Secure Payments
  • Satisfaction Guarantee
  • All over India Shipping
Share your love
Guaranteed Safe Checkout

ISO 9001:2015 | ISO 14001:2015 | ISO 45001:2018 | RoHS Certified

Industrial & Railway Battery Charger / Discharger

High-Reliability DC Power Systems for Critical Applications

110V-155V DC | 30 Amp to 500 Amp | IGBT & Thyristor Based

20+ Years of Excellence | Trusted by 500+ Industries Across India

Industrial - Railway Battery Chargers & Dischargers for Critical Power Applications

MAC Power Systems designs and manufactures high-reliabilityย industrial battery chargersย andย charger-cum-dischargersย for critical power applications. Built with conservative design principles and premium components, our systems ensure failsafe operation, long service life, and consistent performance under demanding conditions.

Extensive Range

Wide range of standard and customized models with voltage outputs up to 110V-155 VDC and current outputs up to 500 Amps

High Reliability

Conservative electrical and thermal design with high-quality components and absolute reliability with fail-safe protection

IGBT & Thyristor Based

Advanced rectifier technology with both IGBT and Thyristor-based options for optimal performance

Customizable Solutions

Available in standard and customized configurations for industrial, railway, and infrastructure applications

Battery Charger & Discharger Applications

MAC Battery Chargers and DC systems are designed for versatile use across critical infrastructure and industrial applications.

Process Control Systems

Reliable DC power for industrial automation, SCADA systems, and process control equipment requiring uninterrupted power supply

Railways

Railway battery charging systems for signaling, traction, communication equipment, and station electrical systems

Telecommunications

Battery charging systems for telecom towers, exchanges, and communication networks ensuring 24/7 connectivity

Switchgear Protection

DC power for circuit breaker control, relay protection, and switchgear operation in substations and power distribution

Emergency Lighting Systems

DC power systems for emergency lighting in commercial buildings, hospitals, airports, and critical infrastructure

Power Station Control Systems

DC auxiliary power systems for thermal, hydro, and renewable energy power plants control and monitoring

Technical Specifications - Battery Charger / Discharger

Engineered for reliability, precision, and compliance with international quality standards

โšก Electrical Specifications

Parameter Specification
AC Input Voltage 415 V ยฑ10% VAC
Frequency 50Hz ยฑ 5%
Phase 3 Phase, 4 Wire
DC Output Voltage 110 โ€“ 155 VDC
Output Current 30 Amp โ€“ 500 Amp
Ripple โ‰ค 2% at full load
Efficiency โ‰ฅ 95% at full load
Regulation Within 1% for AC voltage range and 10โ€“100% load variation

๐Ÿ”ง Transformer & Rectifier

Component Details
Main Transformer Copper wound
Insulation Class B / F
Transformer Cooling Natural Air
Rectifier Type 3 Phase, Full Wave, Full Control
Rectifier Elements IGBT | Thyristor Based
Rectifier Cooling Forced Air Cooled

๐Ÿ›ก๏ธ Isolation & Protection

Protection Feature Description
AC Input Protection MCB & Contactor
DC Output Protection HRC Fuse
Rectifier Protection Individual Stack Fuses
Over Voltage Protection Output Over Voltage Trip
Over Load Protection Output Over Load Trip
Thermal Protection Thyristor Stack Over Temperature Trip
Capacitor Protection Filter Capacitor Fuse
Soft Start Yes
Current Limiting Yes

๐Ÿšจ Alarm Indications

Alarm Type Description
AC Input Fail Single Phasing / Phase Unbalance / Phase Reversal (Optional)
Rectifier Fuse Fail Yes
Output Fault Over Voltage / Over Load
Temperature Alarm Thyristor Stack Over Temperature
Capacitor Fuse Fail Yes

๐Ÿ“Š Metering & Monitoring

Meter Provided
Meter โœ“ Yes
AC Input Voltage โœ“ Yes
AC Input Current โœ“ Yes
DC Output Voltage โœ“ Yes
DC Output Current โœ“ Yes

๐Ÿ”จ Construction Details

Item Specification
Wiring 1.1 kV grade multistrand copper, PVC insulated (IS: 694)
Busbars Electrolytic Copper
Enclosure Sheet steel, IP-21 protection
Paint Finish Powder Coated, Siemens Grey (RAL 7032)

๐ŸŒก๏ธ Physical & Environmental

Item Specification
Dimensions (H ร— W ร— D) 1189 ร— 1036 ร— 732 mm (Approx.)
Installation Floor Mounting / Indoor Type
Operating Temperature Up to 50ยฐC
Relative Humidity โ‰ค 90%, Non-condensing

Why Choose MAC Power Systems Battery Chargers?

Years of Excellence

Two decades of proven expertise in power conditioning solutions

ISO Certified

ISO 9001, ISO 14001, ISO 45001, RoHS & CE compliant manufacturing

Made in India

Proudly manufactured in India with global quality standards

Round-the-Clock Support

7 ร— 24 ร— 365 customer service and technical support

Railway Approved

Trusted by Indian Railways with UQ-1906 certification for railway applications

IGBT & Thyristor Technology

Advanced rectifier options with both IGBT and Thyristor-based configurations

Frequently Asked Questions - Battery Charger / Discharger

What is the difference between a battery charger and charger-cum-discharger?
A battery charger only charges batteries, while a charger-cum-discharger can both charge and discharge batteries. The discharge function is essential for battery maintenance, capacity testing, and conditioning. Our systems provide controlled discharge with adjustable current settings for comprehensive battery management.
What is the difference between IGBT and Thyristor-based chargers?
IGBT-based chargers offer faster switching, lower ripple content, and better efficiency (typically >95%). They provide smoother DC output and are ideal for sensitive battery applications. Thyristor-based systems are more robust, cost-effective, and suitable for heavy-duty industrial applications. We offer both technologies based on your specific requirements.
What battery types are compatible with your chargers?
Our battery chargers are compatible with various battery types including VRLA (Valve Regulated Lead Acid), flooded lead-acid, nickel-cadmium, and lithium-ion batteries. The charging parameters can be customized based on battery chemistry, capacity, and manufacturer specifications.
Are these chargers suitable for railway applications?
Yes, our battery chargers are approved for railway applications with UQ-1906 certification. They meet Indian Railway specifications and are widely used in railway signaling systems, traction substations, communication equipment, and station electrical systems across India.
What is the typical efficiency and ripple content?
Our battery chargers deliver โ‰ฅ95% efficiency at full load with ripple content โ‰ค2%. This ensures minimal energy loss, reduced heat generation, and clean DC power that extends battery life. The high efficiency also translates to lower operating costs over the system's lifetime.
Can you provide customized voltage and current ratings?
Absolutely! While our standard range covers 110V-155V DC and 30-500 Amp, we specialize in customized solutions. We can design battery chargers for different voltage levels (12V, 24V, 48V, 220V, etc.) and current ratings based on your specific application requirements.

Reviews

There are no reviews yet.

Be the first to review “Railway Battery Charger – Discharger”

Your email address will not be published. Required fields are marked *

Advanced Power Solutions

Engineered battery chargers, UPS systems, and stabilizers designed for industrial and critical applications.

Reliable Battery Charging Systems

High-performance railway, telecom, and substation battery chargers with long service life and safety compliance.

Industrial-Grade Manufacturing

Robust design, quality-tested components, and strict quality control to ensure dependable performance in harsh environments.

Technical Support & Custom Solutions

Expert consultation, installation guidance, and customized power solutions tailored to your project requirements.